This calculator applies the multiple-enclosure outdoor-air and air-cleaning provisions of AS 1668.2-2012. When several rooms (enclosures) are served by one air-handling unit or fan coil unit that recirculates air, the outdoor air introduced at the system can be less than the simple sum of each room's requirement. This is because air returned from lightly-occupied rooms still carries usable, "residual" outdoor air, which is recycled back into the supply and helps dilute the busier rooms.
The Standard captures this with a multiple-enclosure factor (M) based on the critical enclosure — the room with the highest ratio of required outdoor air to supply air. The calculator computes that factor, the system outdoor-air rate, and — where validated air cleaning is used — the central air-cleaner efficiency needed to support a reduced outdoor-air rate. It is intended for mechanical and building-services engineers, and its results are validated against the worked example in Clause D7 of the Standard.
Sizes the minimum introduced outdoor-air rate (Qf) for a system serving multiple enclosures. Use it as a straight multiple-enclosure outdoor-air-rate calculator.
Finds the required central air-cleaner fractional efficiency (ec) and the Table D1 filter class that allow a reduced introduced outdoor-air rate (7.5 or 2.5 L/s per person).
| Per enclosure | Number of people (n), supply air to the room (qs, L/s), and the Table A1 outdoor-air rate for the space type (qf, L/s per person — e.g. 10 for general office). |
| Air-cleaning | Whether the design uses no air cleaning, particulate filtration only, or particulate plus odour treatment. |
| Optional | Total conditioned floor area (m²) to check the area-based floor of 0.35 L/s.m², and total system exhaust (L/s) for the make-up air check. |
In System Basis, select No air cleaning for a plain outdoor-air-rate result, Particulate filtration only (7.5 L/s/p floor), or Particulate + odour treatment (2.5 L/s/p floor). This sets which method and floor rate apply.
Confirm the Default Table A1 rate (applied to new enclosures). Optionally enter the total floor area to test the 0.35 L/s.m² floor, and the system exhaust so the tool can flag whether the introduced air clears the make-up requirement.
For each room served by the system, add an enclosure and enter people, supply air and the room's Table A1 rate. Use Add Enclosure / the delete icon to match your zone count, or Load D7 Example to see a worked case. The required outdoor air is qmin = qf × n.
Press Run Calculation. The tool identifies the critical enclosure (highest qmin/qs), computes the multiple-enclosure factor M, the introduced outdoor air Qf, and — in air-cleaning mode — the required efficiency ec.
In No air cleaning mode the headline is the minimum introduced outdoor air Qf (L/s). In an air-cleaning mode it is the required ec (%) with the recommended filter class. The metric tiles and the dark System Parameters strip show M, R, rc′, Qs, N and the effective outdoor air Qeff.
The Per-Enclosure Breakdown lists each room's qmin, ratio r and residual outdoor air, and marks the critical room. In an air-cleaning mode, the Table D1 panel shows each filter class against the required ec and highlights the lowest class that meets it.
Use Print / Save PDF to produce an A4 record of the inputs and results for the project file. The layout reformats automatically for printing.
| rc′ | The critical ratio — the highest qmin/qs of any enclosure. The busiest room relative to its supply governs the whole system. |
| M | The multiple-enclosure factor, 1 / (1 + R − rc′). It credits the residual outdoor air recycled from over-ventilated rooms. |
| Qf | The fresh outdoor air drawn in at the system intake (the FCU/AHU). This is the design outdoor-air setting. |
| Qeff | The effective outdoor air carried in the supply (rc′ × Qs). It is larger than Qf because recycled air tops it up — the supply still delivers the critical room its full required fraction. |
| ec | The fractional efficiency a central air cleaner must achieve so that a reduced Qf still meets Qeff. Air-cleaning modes only. |
| Filter class | The lowest AS 1668.2 Table D1 class whose efficiency meets ec. F-classes run F5 (40%) to F9 (95%); below 40% sits the "Undefined" coarse band. |
Implements the Appendix D (normative) procedure: determines the required central air-cleaner fractional efficiency (ec) and the Table D1 filter class so that recycled air can offset a reduced introduced outdoor-air rate across enclosures on a common air-handling system. Select No air cleaning to use it purely as a multiple-enclosure minimum outdoor-air-rate calculator (Cl. 2.8.5.3). Validated against the Standard's Clause D7 worked example.
Enter enclosure data and tap Run Calculation