AS 1668.2-2012 CENTRAL AIR CLEANER FILTER EFFICIENCY FOR REDUCED OUTDOOR AIR AND MULTIPLE ENCLOSURE CALCULATIONS


This calculator applies the multiple-enclosure outdoor-air and air-cleaning provisions of AS 1668.2-2012. When several rooms (enclosures) are served by one air-handling unit or fan coil unit that recirculates air, the outdoor air introduced at the system can be less than the simple sum of each room's requirement. This is because air returned from lightly-occupied rooms still carries usable, "residual" outdoor air, which is recycled back into the supply and helps dilute the busier rooms.

The Standard captures this with a multiple-enclosure factor (M) based on the critical enclosure — the room with the highest ratio of required outdoor air to supply air. The calculator computes that factor, the system outdoor-air rate, and — where validated air cleaning is used — the central air-cleaner efficiency needed to support a reduced outdoor-air rate. It is intended for mechanical and building-services engineers, and its results are validated against the worked example in Clause D7 of the Standard.

Step-by-Step

Running a calculation